10A NCAC 13K .1211 ADDITIONAL PLUMBING REQUIREMENTS/HOSPICE INPATIENT UNITS
Hospice inpatient facilities or units shall provide a flow of hot water within safety ranges specified as follows:
(1) Patient Areas – 6 ½ gallons per hour per bed and at a temperature of 100 to 116 degrees F;
(2) Dietary Services – 4 gallons per hour per bed and at a minimum temperature of 140 degrees F; and
(3) Laundry Area – 4 ½ gallons per hour per bed and at a minimum temperature of 140 degrees F.
History Note: Authority G.S. 131E‑202;
Eff. June 1, 1991;
Readopted Eff. October 1, 2021.